Product Introduction
When power supply failures cause costly downtime in industrial control systems, the GE IC200PWR101 provides robust protection and reliable operation. This Versamax series module converts 120/240 Volts AC input into stable 5 Volts DC and 3.3 Volts DC outputs, ensuring continuous power to PLC rack backplane devices. With short circuit and overload protection, it prevents damage from common electrical faults. The 20-millisecond holdup time allows critical data to be saved during brief outages, minimizing disruption.
Technical Specifications Breakdown
Below are the key performance metrics of the GE IC200PWR101 power supply module. All values are directly from the manufacturer’s specifications.
| Parameter |
Value |
| Input Voltage |
120/240 Volts AC |
| Output Voltage |
5 Volts DC and 3.3 Volts DC |
| Input Power |
27 volt-amperes |
| Holdup Time |
20 milliseconds |
| Protection |
Short circuit, overload |
| Total Output Current |
1.5 Amperes maximum |
| 3.3V Output Current |
0.25 Amperes maximum |
| 5V Output Current |
1.5 Amperes minus the 3.3 Volts current used |
| Frequency Range |
47 to 63 Hertz |
| Dimensions (W x H x D) |
49 mm (1.93 in) x 133.4 mm (5.25 in) x 39 mm (1.54 in) |
The jumper installation and voltage range determine the input voltage setting. This module does not support extended power or isolated power.
Industry Applications
The GE IC200PWR101 excels in environments where power quality varies. In manufacturing lines, it protects networked I/O and CPU modules from surges, reducing unplanned stops. In process control systems, its 20-millisecond holdup time ensures controllers maintain state during brief voltage dips, preventing data loss or alarm floods. The overload protection is especially valuable in systems with high-inrush peripheral devices.
Installation & Setup Guidance
Mount the GE IC200PWR101 onto a standard Versamax rack backplane using the 49 mm width slot. Before applying power, set the voltage jumper according to your local line voltage (120VAC or 240VAC). Verify that the total current draw on the 5V rail does not exceed 1.5 A minus any 3.3V current used. The module can serve as a main or supplemental power source. When using a power supply booster carrier, configure it as a supplemental supply. Keep the area around the module clear for heat dissipation.
Compatibility & Integration
The GE IC200PWR101 is designed for the GE Fanuc Versamax series. It supplies power to network interface units (NIU), I/O modules, and CPUs connected to the same rack backplane. As both a main and supplemental source, it integrates easily into multi-rack or high-availability systems. No additional hardware is required beyond a compatible Versamax backplane and carrier.
Troubleshooting & Common Issues
If the GE IC200PWR101 trips under load, check for external short circuits on the backplane or a connected device exceeding the 1.5 A total output. Overload indicates a downstream fault—disconnect modules until the supply resets. A blown fuse or persistent failure suggests an internal problem; replace the unit. The holdup time of 20 ms ensures that brief line dips do not cause false resets. For maximum reliability, ensure input voltage is within the specified 120/240 VAC range and frequency between 47-63 Hz.
Selection Guide & Purchasing Advice
Confirm that your application requires a 120/240 VAC input supply with dual outputs. Verify the total current requirements of your backplane devices do not exceed the 1.5 A limit. If you need extended power or isolation, consider other Versamax models. For genuine GE Fanuc parts, trust ubest101 as your reliable supplier of new, sealed industrial automation components.