Product Overview
When unexpected machinery vibrations go undetected, they can lead to costly downtime and catastrophic failures. The Bently Nevada 9200-06-05-10-00 Two-Wire Velocity Seismoprobe Transducer provides early warning by accurately measuring vibration velocity. This industrial automation module is designed for continuous monitoring of rotating equipment, helping operators detect imbalance, misalignment, and bearing wear before they escalate.
Technical Specifications
| Parameter |
Value |
| Sensitivity |
20 mV/mm/s (500 mV/in/s), ±5% |
| Calibration Load |
10 kΩ (Terminal A to B) |
| Sensitivity Temperature Coefficient |
0.2%/°C |
| Dynamic Operating Range |
2.54 mm (0.100 in) peak-to-peak |
| Velocity Range |
25 mm/s (1 in/s) at 100 Hz, 10 kΩ load |
| Coil Resistance |
1.25 kΩ ±5% |
| Locked Coil Inductance |
125 mH typical |
| Operating Temperature (9200) |
-29°C to +121°C (-20°F to +250°F) |
| Humidity |
To 95% noncondensing; 100% non-submerged with integral cable |
| Case Material |
Anodized aluminum A204 |
| Gasket Material |
Neoprene |
| Height |
102 mm (4 in) typical |
| Diameter |
41 mm (1.6 in) typical |
| Weight (9200) |
300 g (10.5 oz) typical |
Industry Applications
In steam turbines, compressors, and large pumps, continuous vibration monitoring is critical. The Bently Nevada 9200-06-05-10-00 excels in detecting early-stage faults. For example, in a 10 MW compressor train, this transducer can identify a 1x running speed imbalance that would otherwise go unnoticed until bearing failure. Its rugged anodized aluminum case and neoprene gasket withstand harsh industrial environments.
Maintenance & Reliability
To maintain accuracy, perform periodic calibration verification every 12 months using a known vibration source. Keep the mounting base clean and ensure the M10X1 stud is torqued to manufacturer specifications. The transducer's dust and moisture resistance supports reliable operation in high-humidity areas, reducing unplanned maintenance events.
Selection Guide & Purchasing Advice
Before ordering, confirm your mounting angle and minimum operating frequency. The 9200-06-05-10-00 variant includes the 06 option (0°±100, 10 Hz), 05 terminal block connector, 10 circular M10X1 base, and 00 agency approval. For proper integration, verify that your monitoring system accepts the 20 mV/mm/s sensitivity output. We recommend sourcing from a trusted supplier like ubest101 to guarantee new, factory-sealed units with full warranty.